{"id":36920,"date":"2026-03-17T05:36:19","date_gmt":"2026-03-17T05:36:19","guid":{"rendered":"https:\/\/trumonytechs.com\/?p=36920"},"modified":"2026-03-17T05:43:44","modified_gmt":"2026-03-17T05:43:44","slug":"heat-pipe-cooling","status":"publish","type":"post","link":"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/","title":{"rendered":"Come funziona il raffreddamento a heat pipe e quando \u00e8 consigliabile utilizzarlo?"},"content":{"rendered":"<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">A heat pipe moves heat from a focused source to a remote rejection surface. It does this passively, with no pump, no fan, and no external power. But whether a heat pipe fits your design depends on four factors. These are working fluid temperature range, installation orientation, wick capillary pressure, and downstream rejection quality.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">We at Trumonytechs assess heat pipe suitability as part of a broader thermal management portfolio. That portfolio includes liquid cold plates and thermal interface materials. Our selection process matches the transport mechanism to the actual power density, orientation envelope, and lifecycle requirements of each project.<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">What Heat Pipes Are and How They Work<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">A heat pipe is a sealed, evacuated metallic vessel. Copper is the most common envelope material for electronics cooling. Aluminum, titanium, and stainless steel also serve as envelope materials, depending on the working fluid and operating temperature. Inside the vessel sits a small charge of working fluid and a capillary wick structure.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">When heat enters the evaporator end, the fluid vaporizes. Vapor travels to the cooler condenser end and releases latent heat. The liquid then returns to the evaporator through the wick by capillary force. No moving parts sustain this cycle.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">This sets heat pipes apart from thermosyphons. Thermosyphons rely on gravity alone to return condensate. They require the condenser to sit above the evaporator. Heat pipes with capillary wicks can operate in orientations that thermosyphons cannot.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">The envelope is also a sealed pressure vessel. Internal pressure varies with the working fluid&#8217;s saturation temperature. The vessel must resist internal vapor pressure at peak temperature and external atmospheric pressure at cold startup.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">A heat pipe&#8217;s effective thermal conductivity can be orders of magnitude higher than solid copper. But the usable value depends on pipe length, diameter, wick structure, and power load. Published ranges vary widely. Treat them as reference points, not fixed material properties. Transport capacity is a system-level output, not a catalog number.<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">Why Thermal Engineers Choose Heat Pipes<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Heat pipes solve a specific problem. They move heat passively over a distance that solid conduction cannot cover within the temperature budget. Four core advantages drive selection:<\/p>\n<ul class=\"[li_&amp;]:mb-0 [li_&amp;]:mt-1 [li_&amp;]:gap-1 [&amp;:not(:last-child)_ul]:pb-1 [&amp;:not(:last-child)_ol]:pb-1 list-disc flex flex-col gap-1 pl-8 mb-3\">\n<li class=\"whitespace-normal break-words pl-2\"><strong>No moving parts, zero power draw:<\/strong>The phase-change cycle sustains itself as long as a temperature gap exists between evaporator and condenser. No fan or pump to fail. This matters most in battery-powered devices, sealed enclosures, and remote sites with no power budget for active cooling.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>High thermal conductivity in a compact form:<\/strong> A copper-water heat pipe moves heat at rates that would need a solid copper bar many times its cross-section. This matters most in tight layouts where routing a thick copper block from source to sink is not feasible.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Long service life, minimal maintenance:<\/strong>Well-made heat pipes with compatible fluid-envelope pairings and verified degassing have shown lifetimes beyond 10\u201315 years under stable conditions. This is a reachable benchmark, not a blanket guarantee. It depends on material quality, process control, and operating environment. Best suited for sealed systems with no maintenance access: 5G base stations, embedded industrial controls, ESS enclosures.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Vibration and shock tolerance:<\/strong>No moving parts and no liquid reservoir exposed to sloshing. Heat pipes handle vibration levels that would shorten the life of pumped liquid loops. Best suited for vehicle-mounted electronics, industrial equipment, and ruggedized systems.<\/li>\n<\/ul>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">We recommend heat pipes when these advantages outweigh the thermal resistance floor that active liquid cooling can reach. The design must be checked through prototype testing under real boundary conditions.<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">How Wick Structure and Working Fluid Determine Performance<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Wick type and working fluid set the ceiling on what a heat pipe can do. The wick controls capillary return pressure, maximum heat flux, and orientation tolerance. The working fluid sets the operating temperature range and latent heat capacity.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Working Fluid Selection<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Each fluid-envelope pairing must be verified for chemical compatibility through life testing. The compatibility issue is fluid-envelope specific, not envelope-universal. Aluminum reacts with water and generates hydrogen gas over time. That makes aluminum-water not compatible. But aluminum-ammonia is a proven, reliable combination.<\/p>\n<ul class=\"[li_&amp;]:mb-0 [li_&amp;]:mt-1 [li_&amp;]:gap-1 [&amp;:not(:last-child)_ul]:pb-1 [&amp;:not(:last-child)_ol]:pb-1 list-disc flex flex-col gap-1 pl-8 mb-3\">\n<li class=\"whitespace-normal break-words pl-2\"><strong>Copper-Water:<\/strong> Practical range ~20\u2013150\u00b0C. Some designers treat 25\u00b0C as the realistic lower bound for full two-phase operation. This is the default for most ground-based electronics cooling.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Aluminum-Ammonia:<\/strong> Practical range ~\u221270\u00b0C to 60\u00b0C. Common in spacecraft thermal control and cold-region industrial systems.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Copper-Methanol:<\/strong> Extends below water&#8217;s practical floor, down to ~\u221240\u00b0C. Used in ground-based electronics that must operate below 20\u00b0C ambient.<\/li>\n<\/ul>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">We specify wick type and envelope material from a compatibility matrix. Life test data must verify the matrix before any design moves to prototyping.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Wick Type Selection<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">In projects where orientation is uncertain at the design stage, we default to sintered wicks. We absorb the cost premium rather than risk a wick redesign after prototype testing.<\/p>\n<ul class=\"[li_&amp;]:mb-0 [li_&amp;]:mt-1 [li_&amp;]:gap-1 [&amp;:not(:last-child)_ul]:pb-1 [&amp;:not(:last-child)_ol]:pb-1 list-disc flex flex-col gap-1 pl-8 mb-3\">\n<li class=\"whitespace-normal break-words pl-2\"><strong>Sintered Powder Wick:<\/strong> Highest capillary pressure. Works well against gravity and at adverse tilt angles. Higher cost. Best fit for variable orientation, high heat flux, and long-life designs.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Axial Groove Wick:<\/strong> Lower capillary pressure. Loses performance beyond ~30\u201345\u00b0 adverse tilt. Lower cost. Best fit for fixed gravity-assisted orientation and cost-sensitive builds.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Mesh \/ Screen Wick:<\/strong> Medium capillary pressure. Moderate tolerance to tilt and horizontal use. Medium cost. Best fit for mid-range orientation and cost requirements.<\/li>\n<\/ul>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-36925 aligncenter\" src=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Wick-Structure-Comparison.webp\" alt=\"Sintered powder, axial groove, and mesh wick cross-sections\" width=\"768\" height=\"573\" srcset=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Wick-Structure-Comparison.webp 768w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Wick-Structure-Comparison-300x224.webp 300w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Wick-Structure-Comparison-16x12.webp 16w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Wick-Structure-Comparison-766x573.webp 766w\" sizes=\"auto, (max-width: 768px) 100vw, 768px\" \/><\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Charge Volume Control<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Charge volume must be precise:<\/p>\n<ul class=\"[li_&amp;]:mb-0 [li_&amp;]:mt-1 [li_&amp;]:gap-1 [&amp;:not(:last-child)_ul]:pb-1 [&amp;:not(:last-child)_ol]:pb-1 list-disc flex flex-col gap-1 pl-8 mb-3\">\n<li class=\"whitespace-normal break-words pl-2\"><strong>Overfilling<\/strong> raises flow resistance.<\/li>\n<li class=\"whitespace-normal break-words pl-2\"><strong>Underfilling<\/strong> causes partial dry-out under peak loads.<\/li>\n<li class=\"whitespace-normal break-words pl-2\">The most common issue we see during design review is an <strong>underspecified fill tolerance<\/strong>. This creates unit-to-unit thermal resistance spread in production volumes.<\/li>\n<\/ul>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">Types of Heat Pipes and When Each Geometry Fits<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Geometry selection depends on power density, installation space, orientation, vibration, and cost. We map these variables to a decision matrix before committing to prototype tooling.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Standard Round Capillary Heat Pipes<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Round capillary heat pipes in the 4\u201312 mm OD range are the default for point-to-remote-sink transport. They serve telecom hardware, industrial controls, and mid-power electronics. They bend around obstacles and are cost-effective at volume. Their limitation is small source contact area. A spreader plate is often needed when the source footprint exceeds the pipe diameter.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">A single pipe&#8217;s transport capacity varies with length, temperature, orientation, bending, and wick design. Published data for a 6 mm sintered wick pipe show 30\u201365W per pipe at moderate lengths in gravity-assisted orientation. This number shifts with every design variable. Using 75% of rated Qmax as a safety margin is common practice. We size heat pipes against specific boundary conditions and confirm with prototype tests.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Flat Heat Pipes<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Flat heat pipes offer a wider contact surface. They fit board-level space constraints where round mounting is impractical. The narrower vapor space creates asymmetric capillary behavior. Wick design must account for this.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Vapor Chambers<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Vapor chambers spread heat from a small, high-flux source across a large planar area. They make sense when spreading resistance through a solid copper base would use too much of the temperature budget. Higher tooling cost and greater thickness limit them to specific use cases. We match vapor chamber recommendations to source footprint and power density rather than applying a fixed geometry rule.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Loop and Pulsating Heat Pipes<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Loop heat pipes (LHPs) separate the evaporator from the condenser transport line. This allows longer transport distances and flexible routing. Pulsating heat pipes (PHPs) use oscillating slug flow instead of capillary return. They show strong potential for vibration-tolerant and adverse-orientation applications in power electronics and EV battery thermal management.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-36924 aligncenter\" src=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Geometry-Types-Overview.webp\" alt=\"Five heat pipe geometries: round, flat, vapor chamber, loop, and pulsating\" width=\"768\" height=\"573\" srcset=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Geometry-Types-Overview.webp 768w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Geometry-Types-Overview-300x224.webp 300w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Geometry-Types-Overview-16x12.webp 16w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Geometry-Types-Overview-766x573.webp 766w\" sizes=\"auto, (max-width: 768px) 100vw, 768px\" \/><\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">Heat Pipe Applications Across Industries<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Heat pipes appear in nearly every sector that needs passive, maintenance-free heat transport. The right fit depends on source power density, installation space, orientation profile, and cost.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Consumer Electronics<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">In laptops, tablets, and smartphones, heat pipes are the dominant passive transport solution. They are thin, bendable, lightweight, and made at consumer-market volumes. A typical laptop routes flattened copper-water pipes from CPU and GPU die pads to a shared finned condenser. That condenser sits at the chassis exhaust. The limiting factor here is rarely the pipe itself. It is condenser airflow and fin density at the rejection end.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Data Centers and Telecom<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Heat pipes extend CPU heat sink reach to chassis-level airflow paths in air-cooled servers. They do this without pumped liquid loops. As server power density climbs above 300\u2013500W per socket, <strong><a class=\"underline underline underline-offset-2 decoration-1 decoration-current\/40 hover:decoration-current focus:decoration-current\" href=\"https:\/\/www.trumonytechs.com\/data-center-liquid-cooling\/\" target=\"_blank\" rel=\"noopener\">direct liquid cooling<\/a><\/strong> is replacing air-cooled heat pipe designs. This shift is happening at the rack level. But heat pipes remain cost-effective in mid-density servers and 5G base station housings where liquid infrastructure is not installed.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Our review of heat pipe fit in data center applications includes rack-level airflow mapping. A correctly sized heat pipe in a poorly managed airflow path fails the same way. An undersized pipe in a well-managed path produces the same result.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">EV Battery and Energy Storage Systems<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Battery and ESS applications present the most demanding heat pipe profile. Though <strong><a class=\"underline underline underline-offset-2 decoration-1 decoration-current\/40 hover:decoration-current focus:decoration-current\" href=\"https:\/\/www.trumonytechs.com\/ev-vs-ess-battery\/\" target=\"_blank\" rel=\"noopener\">EV and ESS batteries<\/a><\/strong> share similar cell chemistries, their thermal management needs differ. Both involve large module footprints, tight installation depth, strict cell-to-cell temperature uniformity, and orientation changes during operation.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">In ESS integration projects our team has completed, heat pipe spreading between cells cut peak temperature variance to under 5\u00b0C. This target is a widely adopted design goal in battery thermal management for cell balance and cycle life. Passive heat pipe cooling works for moderate discharge rates where flux density stays within wick capacity and orientation is controlled. For high-rate fast-charging, active liquid cooling is often needed. Learn more about the full scope of <strong><a class=\"underline underline underline-offset-2 decoration-1 decoration-current\/40 hover:decoration-current focus:decoration-current\" href=\"https:\/\/www.trumonytechs.com\/ev-battery-cooling\/\" target=\"_blank\" rel=\"noopener\">EV battery cooling<\/a><\/strong> challenges and solutions.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-36923 aligncenter\" src=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/EV-Battery-Module-Layout.webp\" alt=\"EV Battery Module Layout\" width=\"768\" height=\"512\" srcset=\"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/EV-Battery-Module-Layout.webp 768w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/EV-Battery-Module-Layout-300x200.webp 300w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/EV-Battery-Module-Layout-18x12.webp 18w, https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/EV-Battery-Module-Layout-766x512.webp 766w\" sizes=\"auto, (max-width: 768px) 100vw, 768px\" \/><\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Industrial Power Electronics<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Power converters, motor drives, and inverters produce focused heat in enclosed cabinets with limited airflow. Heat pipes move that heat to cabinet-wall-mounted sinks or external fin stacks. They do this without breaking the sealed enclosure. This preserves IP-rated protection while keeping thermal performance on target. We assess heat pipe routing and condenser sizing alongside the enclosure&#8217;s ingress protection rating. The thermal path must not compromise the mechanical seal.<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">Operating Limits, Failure Modes, and When to Transition to Liquid Cooling<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Every heat pipe has operating limits. These must be verified against the deployment profile before the design is locked. The most costly error is treating the heat pipe as a standalone cooler. A heat pipe transports heat. It does not reject it. The condenser end still needs a finned heat sink, a cold plate, or forced airflow. Size it for full power at worst-case ambient.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Orientation Limits<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Standard axial groove wicks perform best when gravity assists liquid return. Horizontal operation is acceptable for sintered and mesh designs. Adverse orientation needs verified capillary pressure margin that exceeds the hydrostatic head at the worst-case tilt angle. Dynamic conditions matter too \u2014 vehicle cornering, equipment handling, and seismic loading all count.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">In one EV battery integration review, our team found that the assumed horizontal orientation was inverted during vehicle cornering. The original thermal spec did not capture this. That required a full wick redesign. We now require orientation in the thermal boundary document before wick selection.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Power Density and Dry-Out<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Each wick geometry has a maximum heat flux before evaporation outpaces capillary return. Exceeding it causes abrupt thermal resistance increase, not gradual degradation. We size the safety margin per project using vendor-specific test data. We do not apply a fixed percentage across all designs.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">Ambient Temperature Effects<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">When high ambient conditions shrink the evaporator-to-condenser temperature gap, vapor flow weakens. Thermal resistance climbs. We see this most in outdoor equipment enclosures and high-ambient EV deployments. The fix is to verify the minimum usable temperature gap across the full operating range.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">NCG Buildup<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Non-condensable gas migrates to the condenser over time. It reduces active condenser area and raises thermal resistance. The best fix is strict control of envelope material purity, working fluid grade, and degassing procedure. This must be verified through life testing at the point of manufacture, not assumed from material certificates.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">High-purity copper envelopes paired with degassed water are a proven approach. But fit must be checked against the target application&#8217;s cycling profile and required service life.<\/p>\n<h3 class=\"text-text-100 mt-2 -mb-1 text-base font-bold\">When Heat Pipes Are No Longer Enough<\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Heat pipes become the wrong choice in three situations. Power density exceeds the dry-out limit. Orientation constraints cannot be resolved by wick selection. Or the thermal resistance target drops below what passive two-phase transport can achieve. The crossover point is a design output, not a universal threshold. We evaluate both heat pipe and liquid cold plate options against project-specific conditions before recommending either.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>Fit verification before committing:<\/strong> Confirm orientation margin, including dynamic loads. Verify power density headroom below wick dry-out threshold. Check condenser temperature gap under worst-case ambient. Confirm startup temperature above working fluid operating floor. Verify NCG control through life testing. Size the rejection surface for full load. Confirm envelope pressure integrity across the operating temperature range.<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">Conclusion<\/h2>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Heat pipe cooling delivers passive, maintenance-free heat transport far beyond solid copper. But it only works when wick type, working fluid, orientation envelope, and downstream rejection match the actual deployment conditions. Prototype testing must validate the design.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">We bring<strong><a href=\"https:\/\/www.trumonytechs.com\/pf\/water-cooling-plate\/\" target=\"_blank\" rel=\"noopener\"> liquid cold plate<\/a><\/strong>, <a href=\"https:\/\/www.trumonytechs.com\/thermal-interface-materials\/\" target=\"_blank\" rel=\"noopener\"><strong>thermal interface material<\/strong><\/a>, and system-level integration experience. Our work spans EV battery packs, ESS modules, and industrial power electronics. When heat pipe boundary conditions are tight, we verify orientation margin, power density headroom, and long-term NCG stability. The design does not leave our engineering team until those checks pass.<\/p>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">To find out if heat pipe cooling fits your project, contact us. Send your power dissipation map, orientation constraints, ambient temperature range, and target thermal resistance<\/p>\n<h2 class=\"text-text-100 mt-3 -mb-1 text-[1.125rem] font-bold\">FAQ<\/h2>\n<h3 class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>What is the maximum power a heat pipe can transfer?<\/strong><\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">No universal maximum exists. Capacity depends on diameter, length, wick type, fluid, temperature, and orientation. Size against your boundary conditions and confirm with tests.<\/p>\n<h3 class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>Can heat pipes work upside down or in zero gravity?<\/strong><\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Sintered powder and mesh wicks can. Axial groove designs cannot. Verify capillary pressure margin against the specific tilt angle and heat load.<\/p>\n<h3 class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>How do heat pipes fail?<\/strong><\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Two primary modes: dry-out (abrupt temperature spike) and NCG buildup (gradual resistance increase). Both are preventable through correct wick selection, fill procedure, and envelope specification.<\/p>\n<h3 class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>What is the typical design life?<\/strong><\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">Well-made copper-water heat pipes with high-purity envelopes and verified degassed fill have shown over 10\u201315 years under stable conditions. Extreme cycling requires deployment-specific life testing.<\/p>\n<h3 class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\"><strong>How do I choose between a heat pipe and a liquid cold plate?<\/strong><\/h3>\n<p class=\"font-claude-response-body break-words whitespace-normal leading-[1.7]\">If power density, orientation, and thermal resistance targets all fall within verified passive two-phase limits, heat pipes cost less. They also need less maintenance. Beyond those limits, liquid cooling is more reliable. The crossover is project-specific.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>A heat pipe moves heat from a focused source to a remote rejection surface. It does this passively, with no pump, no fan, and no external power. But whether a heat pipe fits your design depends on four factors. These are working fluid temperature range, installation orientation, wick capillary pressure, and downstream rejection quality. We &#8230; <a title=\"Come funziona il raffreddamento a heat pipe e quando \u00e8 consigliabile utilizzarlo?\" class=\"read-more\" href=\"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/\" aria-label=\"Per saperne di pi\u00f9 su How Does Heat Pipe Cooling Work and When Should You Use It?\">Leggi tutto<\/a><\/p>","protected":false},"author":2,"featured_media":36926,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[191],"tags":[],"class_list":["post-36920","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-liquid-cold-plate-news"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.5 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Heat Pipe Cooling: How It Works, Types &amp; When to Use It<\/title>\n<meta name=\"description\" content=\"Learn how heat pipe cooling works, compare wick types and geometries, and find out when to use heat pipes vs liquid cold plates for EV, ESS, and industrial thermal management.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/\" \/>\n<meta property=\"og:locale\" content=\"it_IT\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Heat Pipe Cooling: How It Works, Types &amp; When to Use It\" \/>\n<meta property=\"og:description\" content=\"Learn how heat pipe cooling works, compare wick types and geometries, and find out when to use heat pipes vs liquid cold plates for EV, ESS, and industrial thermal management.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/\" \/>\n<meta property=\"og:site_name\" content=\"Trumonytechs\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/trumonytechs\/\" \/>\n<meta property=\"article:published_time\" content=\"2026-03-17T05:36:19+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-03-17T05:43:44+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp\" \/>\n\t<meta property=\"og:image:width\" content=\"768\" \/>\n\t<meta property=\"og:image:height\" content=\"573\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/webp\" \/>\n<meta name=\"author\" content=\"Trumonytechs\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@Trumonytechs\" \/>\n<meta name=\"twitter:site\" content=\"@Trumonytechs\" \/>\n<meta name=\"twitter:label1\" content=\"Scritto da\" \/>\n\t<meta name=\"twitter:data1\" content=\"Trumonytechs\" \/>\n\t<meta name=\"twitter:label2\" content=\"Tempo di lettura stimato\" \/>\n\t<meta name=\"twitter:data2\" content=\"12 minuti\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/\"},\"author\":{\"name\":\"Trumonytechs\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#\\\/schema\\\/person\\\/eb4f36f93231f994effde9f9223a8c7b\"},\"headline\":\"How Does Heat Pipe Cooling Work and When Should You Use It?\",\"datePublished\":\"2026-03-17T05:36:19+00:00\",\"dateModified\":\"2026-03-17T05:43:44+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/\"},\"wordCount\":2396,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/Working-Principle-Cutaway.webp\",\"articleSection\":[\"Liquid Cold Plate News\"],\"inLanguage\":\"it-IT\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/\",\"url\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/\",\"name\":\"Heat Pipe Cooling: How It Works, Types & When to Use It\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/Working-Principle-Cutaway.webp\",\"datePublished\":\"2026-03-17T05:36:19+00:00\",\"dateModified\":\"2026-03-17T05:43:44+00:00\",\"description\":\"Learn how heat pipe cooling works, compare wick types and geometries, and find out when to use heat pipes vs liquid cold plates for EV, ESS, and industrial thermal management.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#breadcrumb\"},\"inLanguage\":\"it-IT\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"it-IT\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/Working-Principle-Cutaway.webp\",\"contentUrl\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2026\\\/03\\\/Working-Principle-Cutaway.webp\",\"width\":768,\"height\":573,\"caption\":\"Heat pipe internal structure and evaporation-condensation cycle\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/pt\\\/heat-pipe-cooling\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.trumonytechs.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"How Does Heat Pipe Cooling Work and When Should You Use It?\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#website\",\"url\":\"https:\\\/\\\/www.trumonytechs.com\\\/\",\"name\":\"Trumonytechs\",\"description\":\"Thermal Management System Solutions\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.trumonytechs.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"it-IT\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#organization\",\"name\":\"Trumonytechs\",\"url\":\"https:\\\/\\\/www.trumonytechs.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"it-IT\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2022\\\/06\\\/10001-1.png\",\"contentUrl\":\"https:\\\/\\\/www.trumonytechs.com\\\/wp-content\\\/uploads\\\/2022\\\/06\\\/10001-1.png\",\"width\":492,\"height\":250,\"caption\":\"Trumonytechs\"},\"image\":{\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/www.facebook.com\\\/trumonytechs\\\/\",\"https:\\\/\\\/x.com\\\/Trumonytechs\",\"https:\\\/\\\/www.youtube.com\\\/channel\\\/UC2SyZohc9uTwFxzdTMLLlhw\",\"https:\\\/\\\/www.linkedin.com\\\/company\\\/81891179\\\/\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.trumonytechs.com\\\/#\\\/schema\\\/person\\\/eb4f36f93231f994effde9f9223a8c7b\",\"name\":\"Trumonytechs\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"it-IT\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g\",\"caption\":\"Trumonytechs\"}}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Raffreddamento a tubo di calore: come funziona, tipologie e quando utilizzarlo","description":"Scopri come funziona il raffreddamento a tubi di calore, confronta i tipi e le geometrie degli stoppini e scopri quando utilizzare i tubi di calore rispetto alle piastre di raffreddamento a liquido per la gestione termica di veicoli elettrici, sistemi di accumulo di energia e applicazioni industriali.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/","og_locale":"it_IT","og_type":"article","og_title":"Heat Pipe Cooling: How It Works, Types & When to Use It","og_description":"Learn how heat pipe cooling works, compare wick types and geometries, and find out when to use heat pipes vs liquid cold plates for EV, ESS, and industrial thermal management.","og_url":"https:\/\/www.trumonytechs.com\/it\/heat-pipe-cooling\/","og_site_name":"Trumonytechs","article_publisher":"https:\/\/www.facebook.com\/trumonytechs\/","article_published_time":"2026-03-17T05:36:19+00:00","article_modified_time":"2026-03-17T05:43:44+00:00","og_image":[{"width":768,"height":573,"url":"https:\/\/trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp","type":"image\/webp"}],"author":"Trumonytechs","twitter_card":"summary_large_image","twitter_creator":"@Trumonytechs","twitter_site":"@Trumonytechs","twitter_misc":{"Scritto da":"Trumonytechs","Tempo di lettura stimato":"12 minuti"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#article","isPartOf":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/"},"author":{"name":"Trumonytechs","@id":"https:\/\/www.trumonytechs.com\/#\/schema\/person\/eb4f36f93231f994effde9f9223a8c7b"},"headline":"How Does Heat Pipe Cooling Work and When Should You Use It?","datePublished":"2026-03-17T05:36:19+00:00","dateModified":"2026-03-17T05:43:44+00:00","mainEntityOfPage":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/"},"wordCount":2396,"commentCount":0,"publisher":{"@id":"https:\/\/www.trumonytechs.com\/#organization"},"image":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#primaryimage"},"thumbnailUrl":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp","articleSection":["Liquid Cold Plate News"],"inLanguage":"it-IT","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/","url":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/","name":"Raffreddamento a tubo di calore: come funziona, tipologie e quando utilizzarlo","isPartOf":{"@id":"https:\/\/www.trumonytechs.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#primaryimage"},"image":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#primaryimage"},"thumbnailUrl":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp","datePublished":"2026-03-17T05:36:19+00:00","dateModified":"2026-03-17T05:43:44+00:00","description":"Scopri come funziona il raffreddamento a tubi di calore, confronta i tipi e le geometrie degli stoppini e scopri quando utilizzare i tubi di calore rispetto alle piastre di raffreddamento a liquido per la gestione termica di veicoli elettrici, sistemi di accumulo di energia e applicazioni industriali.","breadcrumb":{"@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#breadcrumb"},"inLanguage":"it-IT","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/"]}]},{"@type":"ImageObject","inLanguage":"it-IT","@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#primaryimage","url":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp","contentUrl":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2026\/03\/Working-Principle-Cutaway.webp","width":768,"height":573,"caption":"Heat pipe internal structure and evaporation-condensation cycle"},{"@type":"BreadcrumbList","@id":"https:\/\/www.trumonytechs.com\/pt\/heat-pipe-cooling\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.trumonytechs.com\/"},{"@type":"ListItem","position":2,"name":"How Does Heat Pipe Cooling Work and When Should You Use It?"}]},{"@type":"WebSite","@id":"https:\/\/www.trumonytechs.com\/#website","url":"https:\/\/www.trumonytechs.com\/","name":"Trumonytechs","description":"Soluzioni per sistemi di gestione termica","publisher":{"@id":"https:\/\/www.trumonytechs.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.trumonytechs.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"it-IT"},{"@type":"Organization","@id":"https:\/\/www.trumonytechs.com\/#organization","name":"Trumonytechs","url":"https:\/\/www.trumonytechs.com\/","logo":{"@type":"ImageObject","inLanguage":"it-IT","@id":"https:\/\/www.trumonytechs.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2022\/06\/10001-1.png","contentUrl":"https:\/\/www.trumonytechs.com\/wp-content\/uploads\/2022\/06\/10001-1.png","width":492,"height":250,"caption":"Trumonytechs"},"image":{"@id":"https:\/\/www.trumonytechs.com\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.facebook.com\/trumonytechs\/","https:\/\/x.com\/Trumonytechs","https:\/\/www.youtube.com\/channel\/UC2SyZohc9uTwFxzdTMLLlhw","https:\/\/www.linkedin.com\/company\/81891179\/"]},{"@type":"Person","@id":"https:\/\/www.trumonytechs.com\/#\/schema\/person\/eb4f36f93231f994effde9f9223a8c7b","name":"Trumonytechs","image":{"@type":"ImageObject","inLanguage":"it-IT","@id":"https:\/\/secure.gravatar.com\/avatar\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/445be3cb03a359def23944fc922a17ae56a3eab013b1959243c75737563ea1de?s=96&d=mm&r=g","caption":"Trumonytechs"}}]}},"_links":{"self":[{"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/posts\/36920","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/comments?post=36920"}],"version-history":[{"count":0,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/posts\/36920\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/media\/36926"}],"wp:attachment":[{"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/media?parent=36920"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/categories?post=36920"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.trumonytechs.com\/it\/wp-json\/wp\/v2\/tags?post=36920"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}